AVENTICS | Bus Coupler AES/Valve Driver AV, EtherNet/IP | R412018139–BAL–001–AF
The query "Parameter lesen" (read parameters) takes a few milliseconds since this process triggers
the internal call "Parameter vom Modul neu einlesen" (read in parameters from module again).
The most recently read-out data is transferred.
Thus, execute the query "Parameter lesen" (read parameters) twice in 1 s intervals to read out
the current parameter data from the module.
If you only execute the query "Parameter lesen" once, in the worst case, the parameters that were
read in the last time the device was restarted will be returned.
Table 13:
Writing and reading out module parameters
Field name in the software
window
Service code
Class
Instance
Attribute
Parameter data record
The parameters and configuration data are not saved locally by the bus coupler. They must
be sent from the PLC to the bus coupler and the installed modules on startup.
PLC Configuration of the Valve System
Value in input field to write
parameter
0x10
0x64
Module number in hexadecimal
coding
(e.g. module no. 15 = 0x0F)
0x01
Volume of module parameter data
to be written
Value in input field to read out
parameter
0x0E
0x64
Module number in hexadecimal
coding
(e.g. module no. 18 = 0x12)
0x02
Volume of module parameter data
to be read
85