Type of unit
Temp control
Parameter H01
probe
0= air/air
B1
1= air/air heat pump
B1
(cooling/heating)
2= air/water Chiller
B1/B2 single circuit
(B1/B5 two circuits)
3= air/water heat pump
B1/B2 single circuit
(cooling/heating)
(B1/B5 two circuits)
4= water/water Chiller
B1/B2 single circuit
(B1/B5 two circuits)
5= water/water heat
B1/B2 single circuit
pump rev. on gas
(B1/B5 two circuits)
cooling
heating
B1/B2 single circuit
(B1/B5 two circuits)
6= water/water heat
B1/B2 single circuit
pump rev. on H
O
B1/B5 two circuits
2
cooling
heating
B3
7= Air-cooled
-
condensing unit
8= Air-cooled
-
condensing unit
rev. on gas
9= Water-cooled
-
condensing unit
10= Water-cooled
-
condensing unit rev.
on gas
- Valores mín/máx de tensión y presión
De /09 a /12: establece la tensión y la presión mínima/máxima para la
señal proporcional.
- Calibración de la sonda
De /13 a /20: calibra la sonda correspondiente (de B1 a B8).
- Filtro digital
/21: Establece el coeficiente utilizado en el filtrado digital del valor
medido. Los valores altos de este parámetro eliminarán las posibles
interferencias de las entradas analógicas (sin embargo disminuirá la rapi-
dez de la medición). El valor recomendado es 4 (predeterminado).
- Límite de entrada
/22: Establece la variación máxima que puede ser medida por las son-
das en un ciclo de programa de la unidad; en la práctica, las variacio-
nes máximas permitidas en la medición están entre 0,1 y 1,5 unidades
(bar, °C o °F, dependiendo de la sonda y de la unidad de medida. El
valor recomendado es 8 (predeterminado).
- Unidad de medida
/23: Selecciona la unidad de medida entre grados centígrado o
Fahrenheit. Cuando se modifica el parámetro, el µC
camente la conversión de los valores leídos por las sondas de tempe-
ratura NTC B1, B2, B3 en la nueva unidad de medida; mientras los
demás parámetros configurados (puntos de consigna, diferencial, etc.)
permanecen invariables.
Antihielo, resistencia auxiliar: parámetros (A*)
- Establece la alarma antihielo (temp. ambiente baja para las uni-
dades aire/aire)
A01: Representa la temperatura (punto de consigna antihielo) del agua
a la salida del evaporador por debajo de la cual se activa una alarma
Antifreeze
Cond. temp
probe
probe
1st circuit
1st circuit
B2 (low outlet
B3
temperature)
B2 (low outlet
B3
temperature)
B2
B3
B2
B3
B2
Not used
B2
B3
B3
B3
B2
Not used
B2
Not used
-
B3
-
B3
-
B3
B3
B3
- Min/max voltage and pressure values
From /09 to /12: sets the minimum/maximum voltage and pressure for
the ratiometric signal.
- Probe calibration
From /13 to /20: calibrates the corresponding sensor (from B1 to B8).
- Digital filter
/21: Establishes the coefficient used in the digital filtering of the value
measured. High values for this parameter will eliminate any continuous
disturbance at the analogue inputs (however decrease the promptness
of measurement). The recommended value is 4 (default).
- Input limit
/22: Establishes the maximum variation that can be measured by the
probes in one unit program cycle; in practice, the maximum variations
allowed in the measurement are between 0. 1 and 1.5 units (bars, °C
or °F, depending on the probe and the unit of measure) approximately
every one second. Low values for this parameter will limit the effect of
impulsive disturbance. Recommended value 8 (default).
- Unit of measure
2
efectúa automáti-
/23: Selects the unit of measure as degrees centigrade or Fahrenheit.
When the parameter is modified, the µC
the values read by the NTC temperature probes B1, B2, B3 into the new
unit of measure; while all the other parameters set (set point, differential
etc. ) remain unchanged.
Antifreeze, auxiliary heater: parameters (A*)
- Antifreeze alarm set point (low ambient temp. for air/air units)
A01: This represents the temperature (antifreeze set point) of the water
40
Press. probe Antifreeze
1st circuit
probe
2nd evaporator 2nd circuit
B4
Not used
B4
Not used
B4
B6
B4
B6
Not used
B6
B4
B6
B4
B7
B4
B6
B4
B6
B4
-
B4
-
B4
-
B4
B7
at the evaporator outlet below which an antifreeze alarm is
activated; in this condition the compressors corresponding to the
circuit in question are stopped, while the pump remains on to
Cond. temp
Press. probe
probe
2nd circuit
B7
B8
B7
B8
B7
B8
B7
B8
Not used
Not used
B7
B8
B7
B8
Not used
B8
Not used
B8
B7
B8
B7
B8
B7
B8
B7
B8
Tab 5.1
2
automatically converts
- cod. +030220420 - rel. 2.1 - 17.01.05
µC
2