Selective switching-off of luminaires
To switch-on a luminaire, follow these steps:
Connect the programmer to the zone where the luminaire we want to operate on is installed:
From the screen "LUMINARY MENU" "OPERATION IN LUMINARY" (see "Operations on luminaires") with
the scroll buttons select "TURN OFF".
Press "OK" to confirm the selected option.
The following screen appears:
Enter the number of the luminaire you want to switch-off (three digits), from 001 to 125.
Press "OK" to confirm the number entered. At this moment, the programmer switches-off the selected
luminaire.
If the operation has been correctly carried out, the LED ERR will be off. If the operation is not correctly carried
out, this LED ERR will be ON.
Once the luminaire is switched-on, you can follow switching-on other luminaires.
Press "ANUL." to return to the main screen "OPERATION IN LUMINARY".
The switching-off operation can be run on both lights that are connected to mains supply and those that are not.
Aborting test in progress of one or several luminaires.
To abort a test in progress on one or several luminaires, follow these steps:
Launch a switching-off command (see previous chapter, "Switching-off of luminaire") on the luminaires you
want to abort the test.
If a luminaire has an emergency lamp failure registered, and a test is being run (duration or emergency lamp),
and if you abort this test by means of switch-off command, the luminaire will turn into alert mode and the
emergency lamp failure will still be registered.
If a luminaire has a duration failure registered, and a test is being run (duration or emergency lamp), and if you
abort this test by means of switch-off command, the luminaire will turn into alert mode and the duration failure
will still be registered. The failure will not be corrected until a duration test is completed.

Selective reset of luminaires.

To reset a luminaire, follow these steps:
Connect the programmer to the zone where the luminaire we want to operate on is installed:
From the screen "LUMINARY MENU" "OPERATION IN LUMINARY" (see "Operations on luminaires") with
the scroll buttons select "RESET".
The following screen appears:
Enter the number of the luminaire you want to switch-off (three digits), from 001 to 125.
Press "OK" to confirm the number entered. At this moment, the programmer resets the selected luminaire.
If the operation is not correctly carried out, this LED ERR will be ON.
Once the luminaire is reset, you can follow resetting other luminaires.
Press "ANUL." to return to the main screen "OPERATION IN LUMINARY".
The reset operation can be run on both lights that are connected to mains supply and those that are not.
To check the status of the luminaires after a reset, see "General reset of luminaires".