Installation of optional communication cards (66102/66104/66846)

Remote Power Off communication port (9)

Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.
In order to fully de-energize MX Frame with the RPO port, it is necessary to use a two-position switch (Normally Open
or Closed contact). Once switch is energized/de-energized, the UPS shuts off the display and the output of the UPS.
The output devices can be powered again through auto bypass when the two-position switch is released (open or
closed).
The output devices will remain powered < 1 sec. after RPO activation.
Push the start button to return to normal operation.
Note: The internal batteries will remain connected to the power sub-module after RPO activation.
The cable is not included.
Remote power off contact normally open (9)
RJ12
5 V DC to 27 V DC
Signal:
activation voltage: 5 V DC to 27 V DC,
current: 10 mA max.
Consult EATON for communication cards.
It is not necessary to shutdown the UPS before
installing a communications card.
1. Remove the slot cover(s) secured by two
screws.
2. Insert the optional communication card(s) (48)
in the slot(s) (2).
2
3. Secure the card(s) with both screws.
Remote power off contact normally closed (9)
+
_
RJ12
5 VDC to 27 VDC
86-87021-00 A01 - Page 19
+
_