2.10 Extended Battery Connections

Optional Extended Battery Module Contents
54
(43) Product documentation
(45) Telescopic rails for rack enclosure with
mounting hardware (optional)
(50) MX EXB RT battery module
(52) Battery cable
Follow steps below for connecting one battery module to the MX Frame.
1.
Check that the battery circuit breaker (13) is OFF ("0" position).
2.
Connect the long battery power cable (61) to connectors (9) of the MX Frame and (12) of the battery module, and secure
using screws.
4.
Connect the long battery detection cable (62) to connectors (6) of the MX Frame and (11) of the battery module.
5.
Close the battery circuit breaker (13) ("I" position).
86-87021-00 A01 - Page 24
52
50
45
11
13
12
52
53
62
61
6
9
(87103)
53
43
(53) Battery detection cable
(54) Stabilizer bracket (4 screws included)
(61) Long battery power cable (purchased eparately)
(62) Long battery detection cable
Note: It is not necessary to shutdown the UPS in
order to install the extended battery module.
Up to three batteries may be connected to each
power module on the MX Frame. The illustration
shows connections for two battery cabinets per
module.
Shown for 16U
(68528)
61
62
One EXB must be added
for each 5kVA power
sub module.