2.7
Required Protective Devices and Cable Cross-Sections
Recommended upstream protection – 16U Frame
UPS Power Rating
15000/20000 VA
Required cable cross-sections 16U Frame
Terminal-block cable capacity: 25 mm
◗
Capacity for ground conductor: 25 mm
◗
Recommended upstream protection – 10U Frame
UPS Power Rating
5000/10000 VA
The indicated protection ensures discrimination for each output circuit downstream of the UPS. If these recommenda-
tions are not followed, protection discrimination is not achieved and may result in a potential power interruption to the
connected devices.
Required cable cross-sections 10U Frame
Terminal-block cable capacity: 13 mm
◗
Capacity for ground conductor: 13 mm
◗
2.8
System Installation
UPS with Common Normal and Bypass AC inputs
Main low-
voltage
switchboard
(MLVS)
Note: If using this configuration, do not remove the metal jumper (A).
Frequency converter (without Bypass AC input)
Configuration used when the frequency of the application differs from the Mains (Example: marine requirements).
Main low-
voltage
switchboard
(MLVS)
Note: If using this configuration, remove the metal jumper (A).
86-87021-00 A01 - Page 20
Upstream Circuit
Breaker
125 A
, solid or stranded wire (maximum AWG 2).
2
, solid or stranded wire (maximum AWG 2).
2
Upstream Circuit
Breaker
60 A
, solid or stranded wire (maximum AWG 6).
2
, solid or stranded wire (maximum AWG 6).
2
Bypass AC
Factory Installed
Metal Jumper
A
Normal AC
Remove the
Factory Installed
Metal Jumper
A
Normal AC
2 poles circuit breaker
G L2 (N)
L1
2 poles circuit breaker
G L2 (N)
L1
L1
To UPS Normal AC source
L2 (N)
L1
To UPS Normal AC source
L2 (N)
Load
Load