Return To Normal Ac Source; Ups Shutdown When Ac Present; Ups Shutdown When On Battery - Eaton Pulsar Serie Manual De Instalación Y De Usuario

Ocultar thumbs Ver también para Pulsar Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.4

Return to Normal AC Source

After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been disabled
via UPS personalization) and the load is supplied again. If function is disabled, see Section 3.1, Initial Start-Up.
3.5

UPS Shutdown When AC Present

Before shutdown, please read ALL instructions below:
LOAD UNPROTECTED
00.0 KVA/00% LOADED
ON AUTO BYPASS
PRESS ( I ) to START
33
3.6

UPS Shutdown When on Battery

Before shutdown, please read ALL instructions below:
LOAD UNPROTECTED
00.0 KVA/00% LOADED
ON AUTO BYPASS
PRESS ( I ) to START
33
86-87021-00 A01 - Page 28
22
34
28
22
34
28
1. Press and hold the "0" (OFF) button (28) for 3 seconds.
The buzzer beeps once.
The load is no longer protected by the UPS. It is powered via the
Normal AC source (bypass). If the UPS is set in frequency converter
mode, the equipment
will not be powered. If the Normal AC source is out of tolerance,
the UPS will generate a 10ms output calibrated break.
LEDs (22) is ON. LEDs (33) and (34) are green.
For a full shutdown of UPS and connected load, turn off the
upstream circuit breaker (not included), or remove
the Normal AC source. Turn off the input switch.
1. Press and hold the "0" (OFF) button (28) for 3 seconds.
The buzzer beeps once.
2. The display asks for confirmation – "ARE YOU SURE?".
3. Press the scroll button (25) to select yes.
4. Press confirm button (27).
The UPS is now fully shut down.