2.1.2 Special service conditions
For use under operating conditions other than those specified in item 2.1.1, the recommendations below must
be followed.
1. Special ambient temperature:
If the ambient temperature exceeds + 40 °C, reduce the rated current following the values indicated in table A.
2. Special altitude:
In installations in locations with altitudes above 2,000 m, the thermal dissipation capacity of the product is
reduced, and the dielectric strength of the air reduces the durability of the insulation. Contact us for further
details.
Horizontal position terminal - Temperature (°C) x Current (A)
Ambient
Temperature
40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
According to IEC 60947-2 and the maximum temperature rise in the terminal connection point to the busbar is 70 K.
2.2 ALTITUDE AND INSULATION DISTANCE
2.2.1 Altitude
The ABW Compact is designed for operation at altitudes below 2000 m. At altitudes higher than 2000 m, change
the nominal values under a service condition.
Altitude - h
Rated operational voltage (V
Insulation voltage (V)
Rated current reduction factor
12 | ABWC Compact Air Circuit Breaker
ABWC08
ABWC16
800
1600
800
1600
800
1600
800
1550
800
1500
800
1450
800
1390
Table 2.1: ABWC Temperature Correction Factor Table
h ≤2,000 m
h ≤3,000 m
h ≤4,000 m
h ≤5,000 m
Vertical position terminal - Temperature (°C) x Current (A)
Ambient
Temperature
40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
690
590
520
460
Table 2.2:
ABWC08
ABWC16
800
1600
800
1600
800
1600
800
1600
800
1600
800
1550
800
1500
1,000
1.00
900
0.99
700
0.96
600
0.94