1. Pressing the MENU key five times from the Measurement display leads to the
Options display.
2. On the first screen you can set the OCGR "Lock Time".
M
3. Adjustable range: 0~60s.
5
4. Default value set: 0s.
5. After pressing Enter, the range value can be set by pressing the up and down
keys".
1. The OCGR operating mode can be set by pressing the up key once from the
Options screen.
M
5
2. Modes: Trip/Alarm
3. Default value set: Trip
1
4. After pressing Enter, the value can be changed by pressing the up and down
keys.
1. The thermal operating mode can be set by pressing the up key twice from the
M
Options screen.
5
2. Default value set: 49
2
3. After pressing Enter, the value can be changed by pressing the up and down
keys.
1. The thermal operating mode can be set by pressing the up key three times from
the Options screen.
M
5
2. Modes: Hot / Cold
3. Default value set: Cold
3
4. After pressing Enter, the value can be changed by pressing the up and down
keys.
1. The thermal operating mode can be set by pressing the up key four times from
the Options screen.
M
5
2. Modes: Disable / Enable
3. Default value set: Disable
4
4. After pressing Enter, the value can be changed by pressing the up and down
keys.
1. The frequency can be checked by pressing the up key five times on the Options
M
screen.
5
2. Frequency: 60Hz / 50Hz
5
3. This function can only read the value of the dip switch (frequency already set) on
the rating plug.
1. Each display is moved when changed values are saved after pressing Enter.
Table 12.4:
Options
Event list
display
Content
ABWC Compact Air Circuit Breaker | 49
www.weg.net