2.2.2 Insulation distance

When positioning the electrical panel, keep the insulation distance between the ABW Compact and the panel as
indicated in the table.
A
A
Figure 2.1:
Figure 2.2:
Type
A
B
Fixed
50
150
Withdrawable
5
50
Table 2.3:

2.2.3 Minimum insulation distance

The minimum insulation distances between poles must be in accordance with table 2.4.
Figure 2.3:
Insulation voltage (Ui)
Min. insulation distance (X min)
600V
8 mm
1000V
14 mm
Table 2.4:
ABWC Compact Air Circuit Breaker | 13