www.weg.net
10.2 SETTING THE SELECTORS
Type A selector settings
Nº
Selector type
1
Direct current setting
2
Long time pickup current setting
3
Long time delay
4
Short time pickup current setting
5
Short time delay
6
Instantaneous pickup current
7
Earth leakage
8
Earth leakage delay
Nº
Selector type
1
Long time pickup current setting
2
Long time delay
3
Short time pickup current setting
4
Short time delay
5
Instantaneous pickup current
6
Earth leakage
7
Earth leakage delay
10.3 CONNECTOR
Division
CN1
FRONT
Format
No.
38 | ABWC Compact Air Circuit Breaker
Rating plug
Figure 10.2:
Mode
lu
lr
tr
ls
tsd
li
lg
tg
Table 10.1: Type A selector information
Mode
lr
tr
ls
tsd
li
lg
tg
Table 10.2: S type selector information
CN2
TOP
Selector type P and S settings
Adjustable range
(0,5-0,6-0,7-0,8-0,9-1,0) × In
(0,8-0,83-0,85-0,88-0,89-0,9-0,93-0,95-0,98-1,0) × Iu
(0,5-1-2-4-8-12-16-20), s
@ 6 Ir
CAT.B: (1,5-2-3-4-5-6-8-10-off) × Ir
CAT.A: (1,5-2-3-4-5-6-8-Nenhum-off) × Ir
I²t off: (0,05-0,1-0,2-0,3-0,4), s
I²t on: (0,1-0,2-0,3-0,4), s
(2-3-4-6-8-10-12-15-off)× In
(0,2-0,3-0,4-0,5-0,6-0,7-0,8-1-off)× In
I²t off: (0,05-0,1-0,2-0,3-0,4)
I²t on: (0,1-0,2-0,3-0,4)
Adjustable range
(0,4-0,5-0,6-0,7-0,8-0,9-1,0) × In
(0,5-1-2-4-8-12-16-20), s
@ 6 Ir
CAT.B: (1,5-2-3-4-5-6-8-10-off) × Ir
CAT.A: (1,5-2-3-4-5-6-8-Nenhum-off) × Ir
I²t off: (0,05-0,1-0,2-0,3-0,4), s
I²t on: (0,1-0,2-0,3-0,4) , s
(2-3-4-6-8-10-12-15-off)× In
(0,2-0,3-0,4-0,5-0,6-0,7-0,8-1-off) × In
I²t off: (0,05-0,1-0,2-0,3-0,4)
I²t on: (0,1-0,2-0,3-0,4)
CN3
REAR
CN4