8. Technical data

Observe the permissible temperature
Caution
range of the sensors!
Note
Observe the accuracy of the sensor!
Electronics
I2C bus technology
Accuracy
± 1 %
Display
LCD, 2 lines, 2 x 16 characters
Display languages German, English and French
In ppm for measured values of
Indication mode
both sensors
• Operation: 0 to +45 °C
Permissible
temperatures
• Storage: -20 to +65 °C
Permissible
Maximum 90 % at 40 °C (no
relative air
condensation)
humidity
• 230/240 V - 10 %/+ 10 %
(50/60 Hz)
Power supply
• 115/120 V - 10 %/+ 10 %
(50/60 Hz)
Power
Approximately 5 VA
consumption
Material
ABS, resistant to chemicals
(enclosure)
IP65 for wall-mounting
Enclosure class
enclosure
Weight
Approximately 0.8 kg
Screw terminals for cables up
Connections
to maximum 2.5 mm
Permanent sensor monitoring
or automatic sensor test,
Safety functions
interval between tests
adjustable from 0.5 to 14 days

8.1 Signal inputs and outputs

Relay outputs
Signal inputs
Signal outputs

8.2 Setting ranges for alarms / limit values

Switching point for
limit values
2
Alarm relay
Five relay outputs, NO
(normally open); maximum
250 V/6 A, maximum 550 VA
ohmic load
• two relays for the limit
values of each of the two
sensors
• one alarm relay; free
assignment to the limit
values or to sensor test
(see below.
• Two measured value inputs
(for amperometric sensors 1
and 2)
• Two current outputs
(0) 4-20 mA, maximum
load of 400 Ω, assigned to
the 0-5 ppm range
Limit value 1 (preliminary
warning if exceeded) can
be set to any value within
the measuring range.
Limit value 2 (warning if
exceeded) can be set to
any value within the
measuring range.
Limit value 2 can be
delayed between 0-200
seconds.
Hysteresis: 0 - 0.5 ppm.
Limit value 1 and 2 can be
acknowledged. The
acknowledgement is
stored in a list of events.
The alarm relay can be
assigned to any of the limit
values and/or the sensor test.
13