Grundfos Conex DIS-G Instrucciones De Instalación Y Funcionamiento página 22

Ocultar thumbs Ver también para Conex DIS-G:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 56
11.4.5 Selecting the assignments of the alarm
relay
M1 - limit 1
Alarm relay
ON
M1 - limit 2
Alarm relay
ON
M2 - limit 1
Alarm relay
ON
M2 - limit 2
Alarm relay
ON
Sensor fault
Alarm relay
OFF
M2 - limit 1 / - limit 2 are only displayed if the device
is set to "2 sensors".
1. For each item, select whether the alarm relay
should be activated if the corresponding limit
value is exceeded or if a sensor fault occurs by
pressing the [Up] and [Down] buttons.
2. Confirm each item by pressing [OK].
The alarm relay can be assigned to all five
Note
events. All combinations are possible.
22
11.4.6 Setting the confirmability of limit value 2
If limit value 2 is exceeded by one of the two
sensors, a sprinkling installation is usually triggered,
for example to bond the leaking chlorine.
Normally the relay for limit value 2 remains activated
until the measured value drops down below limit
value 2. However, it may be necessary to switch off
the sprinkling installation for example to implement
countermeasures. In this case, limit value 2 can be
set to allow confirmation.
"Confirm" means that the relay for limit value 2 is
deactivated (and therefore also the connected
sprinkling installation) even though the risk caused
by the increased gas concentration remains.
Warning
Mortal danger!
Use this function only if you are certain
that no large gas breakout has occurred!
Limit 2
to receipt
OFF
1. Select whether limit value 2 should be confirmable
or not by pressing the [Up] or [Down] button.
2. Confirm by pressing [OK].

Publicidad

Tabla de contenido
loading

Tabla de contenido