Codes
Fault
F F 2 2 2 2
Control Board
Fault
F F 2 2 5 5
Moisture Sensor
Faults
F F 2 2 7 7
Pressure
Transducer
Error
F F 2 2 8 8
Real Time Clock
Fault, not
displayed, but
logged.
F F 2 2 9 9
RTD Tempera-
ture Alarm
F F 3 3 0 0
RTD Tempera-
ture Fault
F F 3 3 1 1
Input Phase
Loss
F F 3 3 2 2
No Motor
F F 3 3 5 5
Incompatible
Firmware
Possible Causes
EEPROM error
Bluetooth error
Moisture Sensor has detected
moisture or water
External device wired to the
WET SENSOR terminal has sat-
isfied the configured fault
condition
Input is incorrectly configured
Pressure transducer has failed
Pressure transducer is incor-
rectly wired
Pressure transducer signal is
outside of the expected range
Pressure transducer is
disconnected
Incorrect sensor type setting
Internal real time clock is not
programmed
Real time clock battery on Con-
trol Board is loose
Real time clock battery is dead
Motor windings are getting hot •
Motor windings are too hot
DC bus ripple amplitude ex-
ceeds a set value
All three phases have current
below 15% of motor FLA for
250 ms
Motor circuit has open or loose
connection
Firmware of Power board and
Control board are incompatible
Corrective Action
Cycle power to see if fault resets.
Check cable connection between Control Board and Power
Board. Check all programming parameters.
Verify all programming parameters
Reset the drive to factory default settings, refer to
Functions" on page 33
If problem persists, note the sub-fault number on the display
before contacting the FE Service personnel.
Check Moisture Sensor location for moisture or presence of
water. Clean and dry area. Drive will restart when moisture or
water is no longer detected.
Ensure Moisture Sensor input is configured/wired correctly
Check pressure transducer wiring connections; tighten or cor-
rect, if necessary
Ensure sensor type setting is correct
Replace pressure transducer
Ensure battery is properly inserted. If corrected, reconnect to
drive using mobile app to reset the internal clock time
Replace battery. If replaced, reconnect to the drive using the
mobile app to reset the internal clock time
Shut off the system to allow the PMA to cool down
Shut off the system to allow the PMA to cool down
Persistent faults may require pulling the PMA and installing a
cooling sleeve (AIM manual)
Input phase imbalance and loss of phase may indicate similar
issues
Phase imbalance could be caused by an open delta power
supply
Measure and confirm adequate voltage at the drive input (L1-
L2, L2-L3, and L3-L1).
Confirm input power leads are properly inserted into the in-
put power terminal block and confirm proper torque.
Refer to the motor's owner's manual for troubleshooting
Tighten motor connections
Update firmware of boards to latest version
MAINTENANCE
Troubleshooting
"Special
45