Connecting SITRANS LG200
WARNINGS:
• Check the nameplate on your instrument, to verify the approval rating.
• Approved dust-tight and water-tight conduit seals are required for outdoor Type 4/
NEMA 4, IP65.
Notes:
For detailed wiring instructions, please refer to the full Instruction Manual.
Use shielded twisted pair cable: 0.5 to 1 mm² (AWG 22 to 18).
Separate cables and conduits
wiring practices, or electrical codes.
Wiring
11 to 36 V DC

RUN Mode and PROGRAM Mode

SITRANS LG200 has 2 modes of operation: RUN and PROGRAM.
After powering up, the LG200 display changes every 2 seconds to show one of four values:
Status, Level; %Output, and Loop Current. In RUN mode, use arrow keys
from one display to another. The display can also be set to each display individually.
In RUN mode, press arrow keys
Press Enter
to switch to PROGRAM mode (shows an exclamation point ! as the last
character in the top display line.)
In PROGRAM mode, press arrow keys
and to move to the next choice. Hold the arrow keys for rapid scrolling.
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
Page EN-6
1
may be required to conform to standard instrumentation
to scroll to the parameter you would like to edit.
SITRANS LG200 – QUICK START MANUAL
1
to increase or decrease the value displayed
to switch
7ML19985XG81