2. CU 401 control unit

1
2
3
4
5
6
Pos.
Description
1 and 4
Analog inputs and supply for analog sensor
2
GENIbus
3
Pulse counter input
5
RS-232 input
IR communication via Grundfos remote control
6
R100
7
Connection for operator display (OD 401)
8
Connection for UPS battery back-up (PU 102)
9
Connection for power supply (PU 101)
10 and 14 Digital inputs
11 and 12
Relay outputs
13
Module bus
15
Modem*
16
CompactFlash card for application programs
Connection for external communication bus
17
(RS-232, RS-485, etc.)
18
Battery (internal back-up) for clock
* Not standard, but can be ordered from Grundfos.
All manuals and user guides at all-guides.com
7
8
9
14
15
13
12
11
10
Functions
• GENIbus communication (RS-485).
• 2 analog inputs which can be connected
to sensors with current (4-20 mA) or volt-
age (0-10 V).
• 6 digital inputs (24 V).
• 24 V output for sensor supply.
• 10 V output for potentiometer.
• 2 relay outputs (changeover relay) for
alarms for the control of external equip-
ment (400 VAC/2 A) like for instance
revolving warning light or horn.
• Pulse counter input (max. 10 kHz).
• Connection of operator display (OD 401).
• Module bus connection.
• Connection of UPS battery back-up
(optional).
• Communication buses:
- RS-232*
- Profibus-DP slave*
- DeviceNet.*
• Ethernet connection.*
• Modem connection.*
16
17
18
7