Getting started
■
Each action is executed with a programmed heating set point for
a programmed time (steps of 12 hours).
■
A maximum of 20 different actions can be programmed.
■
The program is activated in the test run operation.
■
When the program is stopped by an error or an operation switch
off or a power failure, the U3 error code will be displayed.
To resolve the error codes, see "11.3. Error codes" on page 47.
Procedure
Example of program:
H
(2)
(1)
[F-07]=48 h
[F-07]=24 h
(1)
(2)
[F-06]=25°C
[F-06]=35°C
H Heating set point
t Time
(1) Action number 1
(2) Action number 2
1
Set field settings
■ The different actions are programmed as follows:
(refer to "8.9. Field settings" on page 26 to know how to
change the field settings)
1 Set in [F-05] (Action number), the action to be programmed,
example 1.
Save the new value by pressing the pr button.
2 Set in [F-06] (Heating set point of selected action number
[F-05]), example 25°C.
Save the new value by pressing the pr button.
3 Set in [F-07] (Time of selected action number [F-05]),
example 24 hours.
Save the new value by pressing the pr button.
4 Repeat step 1 through 3 to program all the actions.
INFORMATION
■
The not set actions will not be programmed
because these actions has time [F-07] equal to 0
hours as default.
■
So in case to many actions are programmed and
the quantity needs to be reduced, set the time
[F-07] to 0 hours of the actions that does not
need to be executed.
■ Consult the different actions to confirm good setting values
as follows:
(Refer to "8.9. Field settings" on page 26 to know how to
change the field settings)
1 Set in [F-05] (Action number), the action to be consulted,
example 1.
Save the new value by pressing the pr button.
2 Consult [F-06] (Heating set point of selected number [F-05])
3 Consult [F-07] (Time of selected number [F-05]), example 24
hours.
4 Repeat step 1 through 3 to consult all the actions.
■ Enable the "underfloor heating screed dry-out program" as
follows:
1 Set in [F-08] (Underfloor heating screed dry-out program
enabled/disabled) to 1 (enabled).
2 When finished, press the z button to exit the FIELD SET
MODE.
Installation manual
43
2
Activate
1 Push the z button 4 times so the t icon will be
displayed.
2 To start the "Underfloor heating dry-out program" press the
y button.
3 The "Underfloor heating dry-out program" will start and
display the action and temperature setting of action
number 1. The icon e is also displayed.
3
During activation
The underfloor heating dry-out program will automatically run
trough all programmed actions.
4
End
1 When all actions are executed, the program will automatically
be stopped by switching off the unit and the t icon will be
disappeared.
t
2 When the (Underfloor heating dry-out program) has ended
successfully the [F-09] will have value 21.
INFORMATION
The activation of the "Underfloor heating screed
dry-out program" is similar to the starting the Test run
operation
INFORMATION
■
When the program is stopped by an error, by an
operation switch off or by a power failure, then the U3
error will be displayed.
To resolve the error codes, see "11.3. Error codes" on
page 47.
In this case [F-09] (Latest action number executed)
will contain the latest action executed.
■
[F-08] The "Underfloor heating screed dry-out
program enabled (1)/disabled (0)" is always set to 0
(disable) when a program has been started once. This
means that in case a second time an underfloor
heating screed dry-out program must be started then
[F-08] needs to be set again.
Indoor unit for air to water heat pump system
RKHBH/X008BB