Table 11:

Bus coupler diagnostics display

LED
Signal
SENSOR/
green
LOGIC
POWER
SUPPLY
VALVE
green
POWER
SUPPLY
DDL
off
AVENTICS | DDL, DDL-E | 1987765499–BDL–001–AC
8

Diagnostic

8.1 Bus coupler diagnostics display
The LEDs on the front panel of the bus coupler show the
messages of the following table.
Error
Description
Voltage within tolerance
off
No voltage available
blink
Voltage < 19.2 V or > 28.8 V
Voltage within tolerance
off
No voltage with sensors/logics
blink
Voltage < 21.6 V or > 26.4 V
DDL communication functioning
red
No DDL communication
(See chapter 8.2 Software diagnosis)
The distribution voltage is measured internally at the
BUS OUT X72 connection.
The LED DDL lights up red in the case of an error and
shows that no data communication is taking place on the
DDL. This could be caused by the following:
Different baudrate settings for the individual DDL
W
participants
Spaces in DDL addressing
W
DDL address entered twice
W
DDL addresses 0 and 1-14 assigned at the same time
W
Configuration changed during operation
W
55
Diagnostic