OPERATING INSTRUCTIONS
7.3
Notes on UL approval
en
8
Commissioning
8.1
Alignment
8.2
Adjustment
26
O P E R A T I N G I N S T R U C T I O N S | WTT12-S
L+ = Voltage supply
Q = Digital output
M = Ground
D = Diagnostics/test
n. c. = Not connected
Procedure
1.
Connect the electrical connections.
2.
Apply and switch on the voltage supply (U
The green LED on the sensor lights up.
The device shall be supplied from an isolating transformer having a secondary overcur‐
rent protective device that complies with UL 248 to be installed in the field rated either:
a)
max 5 amps for voltages 0 ~ 20 V (0 ~ 28.3 V peak), or
b)
100 / Vp for voltages of 20 ~ 30 V (28.3 ~ 42.4 V peak).
Alternatively, they can be supplied from a Class 2 power supply.
UL Environmental Rating: Enclosure type 1
Procedure
Align the sensor according to the project planning requirements.
Prerequisites
Sensor is correctly mounted and aligned.
Sensor has a clear view of the reference surface.
Normal operation is active. No teach-in is possible in test mode.
Procedure
NOTICE Do not operate the teach-in button using sharp objects.
1.
Press the teach-in button for 10 seconds.
The distance between the sensor and reference surface L
The two thresholds L
1
LEDs during teach-in
The yellow LEDs behave as follows during teach-in (both displays always switch synchro‐
nously):
As soon as the teach-in button is pressed, the LED switches off
If teach-in is successful, the LED indicates the output state of the sensor
> 0 V).
V
and L
are derived from the taught-in distance L
3
2
1
5
3
4
is taught in.
2
.
2
8029123/2024/01/15 | SICK
Subject to change without notice