5. REMOTE TERMINAL AND SUPERVISORY NETWORK
5.1 Remote display terminal
The display terminal can be detached from the humidifi er and moved up
to 30 m (98 feet) away.
1
2
3
Key:
1 telephone cable 6 wires (up to 30 m / 98 feet distance);
2 two EMC fi lters (code 0907858AXX) to be applied to the ends of the
telephone cable;
3 remote display terminal.
Note: to fi ll the empty space left by the display terminal on the
humidifi er, use CAREL kit code HCTREW0000.
"UE BASIC" +030220632 - rel. 2.3 - 20.01.2009
humiSteam
2
J18
Fig. 5.a
5.2 RS485 supervisory network (M1.1-M1.3)
M.1.1 M.1.2 M.1.3
+ - G0
Important: for the RS485 connections in household (IEC EN
55014-1) and residential (IEC EN 61000-6-3) environments, use
shielded cable (with shield connected to GND). with maximum shielded
cable length: specifi ed by the EIA RS485 protocol, equivalent to European
stan-dard CCITT V11, using shielded twisted pair cable, AWG26, 485 input
stage impedance 1/8 unit-load (with this confi guration, a maximum of
256 devices can be connected) laid in separate conduits from the power
cables