ENG
6.8 Match digit (match between the
softwares of board and terminal)
humiSteam basic verifi es the matching between the softwares of the
controller and the terminal at the start-up. The 8th digits for board and
9th for terminal of both codes must be equal.
If there is no match, on power-up after displaying the software release, and
in normal operation when pressing UP+PRG, the red LED will remain on for 5
seconds, and the following error message will be displayed:
"X – Y", where "X" and "Y" are the 2 diff erent 8th digits. Refer to the after-
sales service.
6.8a Reset cylinder hour counters
Access parameter 'da' (see chap. 7)
press UP and DOWN for 5 seconds
When the counter has been reset, the display shows 'res' .
6.8b Parameters: Saving/recalling the user
settings
From the main screen, a copy of the user settings can be saved at any
time, and then later recalled.
To save the settings::
From the main screen press:
ENTER for 2 seconds,
enter the password 51 using the UP or DOWN button and press ENTER, the
message UbP (Backup User parameters) fl ashes
press ENTER: the message -L- is displayed, fl ashing
press UP or DOWN, the message–S- (Save) is displayed, fl ashing,
press ENTER to save a copy of the user settings, or press ESC to cancel the
operation
NOTE: the copy of the user parameters saved previously will be
overwritten with current user settings.
To recall the settings::
From the main screen press:
ENTER for 2 seconds,
enter the password 51 using the UP or DOWN button and press ENTER,
the message UbP (Backup User parameters) fl ashes
press ENTER: the message -L- (Loading) is displayed fl ashing,
press ENTER to recall the previously saved copy of the user settings, or
press ESC to cancel the operation.
If no button is pressed for 30 seconds, the display returns to the main
screen, without performing the operation.

6.9 Manually drain the water in the cylinder

Partial drain
Press UP and DOWN together for 5 seconds (the message on the display
'dr' indicates the function has been activated). Then hold the two buttons
for the required drain time. To stop, release the buttons.
Total drain
Switch on the humidifi er while holding UP and DOWN until the
appearance of symbols cylinder and drain (the message on the display 'dr'
alternating with 'tot' indicates the function has been activated). To stop
the function before completion press ESC for 5 seconds.