Starting And User Interface; Starting; Stopping; Display - Carel humiSteam Basic Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Before starting the humidifi er, check:
water connections: chap. 2. In the event of water leaks do not start the
humidifi er before having resolved the problem;
steam distribution: chap. 3 and electrical connections chap. 4 .

6.1 Starting

1
ON
2
if the cylinder is new, run a pre-wash cycle by pressing ENTER +
DOWN for 5 sec. (the cylinder is fi lled and emptied three times,
cleaning the inside walls from

6.2 Stopping

1
empty the water in the cylinder to avoid stagnation (see paragraph 6.6
"Manually drain the water in the cylinder").
2
OFF

6.3 Display

humiSteam
μS/cm
Fig. 6.a
Key:
manually drain the cylinder (see paragraph 6.6)
power supply (green LED)
humidifi er operating (yellow LED)
alarm (red LED, not fl ashing)
conductivity value
time in seconds
instant current value in Amperes
real hour counter
steam fl ow-rate (Imperial system)
steam production as a percentage of rated capacity
steam fl ow-rate (international system, default)
parameter programming in progress (parameter setup)
maintenance request (alarm active) or display alarm log (HYS)
3 digits, after 999 the display shows
three digits plus point - between the fi rst and the second
digit- are displayed
).
steam production in progress
cylinder fi lling in progress
foam in the cylinder
presence water in the cylinder
cylinder water drain in progress

6. STARTING AND USER INTERFACE

impurities).
esc
to indicate 1000 (only

6.4 Keypad

key
function
return to the previous display
UP
from the main screen: display the humidifi cation values
(current, conductivity,....), see the following paragraph
from the list of parameters: circular navigation of the
parameters and set the values
DOWN from the main screen: display the humidifi cation values
(current, conductivity,....)
from the list of parameters: circular navigation of the
parameters and set the values
ENTER
for 2 seconds: access the list of parameters
(PRG)
from the list of parameters: select and confi rm (like the
"Enter" key on a computer keyboard)

6.5 Main display

The display on the humidifi er normally shows the current steam
production (kg/h, basic display).
To display other values, press UP or DOWN and scroll the following list:
input signal (0-100%, or ON/OFF if A0=0)
access alarm log (HYS
) (**)
set maximum steam production (parameter P0) (*)
current (A)
conductivity (μS/cm)
cylinder hour counter (h)
To return to the basic display, press ESC.
Parameter C0 (see chap. 7) can be used to change the value of the basic
display (default: current steam production).
(*) To modify the maximum steam output (P0) press:
ENTER (display:
)
UP or DOWN to set the value percentage of production (from 20 to
100%)
ENTER to confi rm the new value
Press ESC to return to the main screen
Parameter P0 can also be accessed from the list of parameters (see chap. 7).
(**) To display the alarm log (HYS ) press:
ENTER (the most recent alarm is shown)
UP or DOWN to scroll the list of alarms in chronological order
press ESC to return to the main screen
To delete the list of alarms press UP and DOWN for 5 seconds (inside the
alarm log), when the list has been reset the display will show 'res' .
6.6 Recalling the manufacturer defaults
From the main screen press ENTER until the password screen is shown:
Enter the password 50
The message dEF is displayed, fl ashing
Confi rm by pressing ENTER or exit by pressing ESC
If no button is pressed for 30 seconds, the display returns to the main
screen.
6.7 Display software release
1) when switching on the unit to display "rel. x.y "(example rel. 1.2)
2) during operation
a) display: from main screen press ESC and UP
b) via network using integer variable 81. Format = # # #. # "(e.g. 12 =
release 1.2)".
17
"UE BASIC" +030220632 - rel. 2.3 - 20.01.2009
ENG

Publicidad

Capítulos

Tabla de contenido
loading