General Features And Models; Humisteam Basic Models And Electrical Specifi Cations - Carel humiSteam Basic Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

11.1 humiSteam Basic models and electrical specifi cations
The following table lists the electrical data relating to the power supply
of the various models and the specifi cations of each. Note that some
models may be powered at diff erent voltages, obviously with diff erent
power input and steam production.
model
steam production
(kg/h)
(2; 4)
UE001
1.5
UE003
3.0
UE005
5.0
UE008
8.0
UE009
9.0
UE010
10.0
UE015
15.0
UE018
18
UE025
25
UE035
35
UE045
45
UE065
65
(1)
tolerance allowed on the rated mains voltage: -15%, +10%;
(2)
tolerance on the rated values: +5%, -10% (EN 60335-1);
(3)
recommended values refer to laying PVC or rubber cables in closed conduits, 20 m
(65.6 feet) long; the standards in force must however be observed,
(4)
rated max instant steam production: the average steam production may be aff ected
by external factors, such as: ambient temperature, water quality, steam distribution
system;
(5)
refer to the wiring diagrams to verify
the data are not absolute and if these diff er from loca
prevail.
TAM confi gurations and connections (transformer for
measuring the current)
Important: the confi gurations and connections are already made
by CAREL, and no changes are required. The following diagrams
represent possible connection modes and may be useful in the event of
serious electrical malfunctions on the humidifi er.
All operations must only be performed by qualifi ed personnel, improper
use may cause serious damage.
one cable turn
cables of the same phase
Fig. 11.a
Important: to avoid interference, separate the power cables
from the probe cables.

11. GENERAL FEATURES AND MODELS

power supply
power
(2)
code
voltage
(1)
(kW)
(V - type)
1.1
D
230 - 1~
2.2
D
230 - 1~
K
230 - 3~
L
400 - 3~
3.7
D
230 – 1~
K
230 - 3~
L
400 - 3~
6.0
K
230 – 3~
L
400 – 3~
6.7
D
230 - 1~
7.5
K
230 – 3~
L
400 – 3~
11.2
K
230 – 3~
L
400 – 3~
13.5
L
400 – 3~
18.7
K
230 – 3~
L
400 – 3~
26.2
K
230 – 3~
L
400 – 3~
33.7
K
230 – 3~
L
400 – 3~
48.7
L
400 – 3~
l standards, the latter must
one turn of the two
two cable turns of the
Fig. 11.b
rated specifi cations
current
(2)
TAM confi guration
(A)
4.9
11.a
100
9.8
11.d
300
5.6
11.a
100
3.2
11.d
100
16.3
11.e
300
9.4
11.c
300
5.4
11.a
100
15.1
11.c
300
8.7
11.a
100
29.3
11.a
500
18.8
11.c
300
10.8
11.d
300
28.2
11.c
500
16.2
11.a
300
19.5
11.a
300
47.1
11.b
500
27.1
11.c
500
65.9
11.c
700
37.9
11.c
500
84.7
11.b
700
48.7
11.c
700
70.4
11.c
700
one cable in "double
same phase
turn" mode
Fig.11.c
33
(5)
cable
(3)
line fuses
(3)
(A /
wiring diagram
(mm
)
type)
2
1.5
10 A / fast-blow
2.5
16 A / fast-blow
2.5
16 A / fast-blow
1.5
10 A / fast-blow
6.0
32 A / fast-blow
2.5
16 A / fast-blow
1.5
10 A / fast-blow
6.0
32 A / fast-blow
2.5
16 A / fast-blow
10.0
40 A / fast-blow
6.0
32 A / fast-blow
2.5
16 A / fast-blow
10.0
40 A / fast-blow
6.0
32 A / fast-blow
6.0
32 A / fast-blow
25
63 A / fast-blow
16
50 A / fast-blow
35
100A / fast-blow
16
60 A / fast-blow
50
75 A / fast-blow
25
80 A / fast-blow
35
100A / fast-blow
three cable turns of the
same phase
Fig.11.d
Fig.11.e
"UE BASIC" +030220632 - rel. 2.3 - 20.01.2009
ENG
(Fig.)
10.a
10.a
10.b
10.c
10.a
10.b
10.c
10.b
10.c
10.a
10.b
10.c
10.b
10.c
10.c
10.d
10.e
10.d
10.e
10.d
10.e
10.e
Tab. 11.a