Cleaning And Maintenance Of The Cylinder; Mechanically Draining The Water In The Cylinder; Cylinder Connection, Three-Phase Models Ue025 To Ue065 - Carel humiSteam Basic Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ENG

9.3 Cleaning and maintenance of the cylinder

Replacement
Important: he cylinder must be only be replaced by qualifi ed
personnel, and with the humidifi er unplugged from the power
supply.
In normal conditions, the disposable cylinders should be replaced after
one year (or 2500 hours of operation, if cleaned periodically), while the
openable cylinders last 5 years (or 10,000 hours of operation, if cleaned
periodically). They must be replaced immediately – even before the
specifi ed intervals – if any anomalies occur. For example, when the lime
scale inside the cylinder prevents the correct fl ow of electric current.
Replacement procedure::
1.
empty all the water (see chap. 6);
2.
turn off the humidifi er (switch "0"), and open the mains disconnect switch
on the power supply (safety procedure);
3.
wait for the humidifi er and the cylinder to cool down;
4.
remove the front cover;
5.
disconnect the electrical cables from the cylinder;
6.
release the cylinder from the locking device and lift it to remove it;
7.
insert the new cylinder (make sure that the model and the power supply
of the new cylinder correspond to the rated data);
8.
fasten the cylinder;
9.
reconnect the electrical cables to the cylinder;
10.
replace the front cover;
11.
switch on the humidifi er;
12.
reset cylinder operating hour counter (see parameters da & db, chap. 7);
13.
Activate the wash new cylinder procedure, pressing ENTER + DOWN for
5 seconds
Periodical checks
After one hour
of operation: check for any signifi cant water leaks.
Every 15 days
or no more than 300 operating hours: check operation,
the absence of signifi cant water leaks, the general conditions of
the casing. Check that during operation there are no arcs or sparks
between the electrodes.
Every 3 months
or no more than 1000 operating hours:
-
disposable cylinders: check operation, the absence of signifi cant
water leaks and if necessary replace the cylinder;
-
openable cylinders: if there are signifi cantly blackened areas, check
the deposits on the electrodes and clean them, using the specifi c
electrode and gasket kit.
Every year
or no more than 2500 operating hours:
-
disposable cylinders: replace;
-
openable cylinders: if there are signifi cantly blackened areas, check
the deposits on the electrodes and clean them, using the specifi c
electrode and gasket kit.
After 5 years
or no more than 10,000 operating hours: replace the
openable cylinder.
After extended operation, or when using water rich in salts, the solid
deposits that naturally form on the electrodes may grow until attaching
to the inside wall of the cylinder. If these deposits are conductive the heat
generated may overheat the plastic until it melts, with the risk of very hot
water being released.
Important: In the event of water leaks, disconnect the power
supply from the humidifi er as the water may conduct electricity.
9.4 Mechanically draining the water in the
cylinder
Drain due to gravity without activating the humidifi er, recommended if:
humidifi er decommissioned;
to empty the cylinder without switching the humidifi er on.
Mechanical drain:
make sure that the humidifi er is not powered;
remove the cover;
activate the mechanical device under the cylinder (see part A, Fig. 9.e).
"UE BASIC" +030220632 - rel. 2.3 - 20.01.2009
Models UE001 to UE018
A
9.5 Cylinder connection, three-phase models
UE025 to UE065
production
conductivity (μS/cm)
(kg/h)
25
75/350 μS/cm
350/1250 μS/cm
35
75/350 μS/cm
350/1250 μS/cm
45
75/350 μS/cm
350/1250 μS/cm
65
75/350 μS/cm
350/1250 μS/cm
The cable ends must be tightened with the top nut to 3 Newton • m.
(units with BL*T5* cylinder only)
A
2
E
1
D
F
C
A
3
B
2
Three-phase and sigle-phase models UE01 to UE018
UE001-3-9
UE005 200...230 V
single-phase
A
D
75...1250 μS
175...350 μS
1 = A
1 = A - E - C
2 = D
2 = B - F - D
UE003 200 - 230 - 400 - 460 V
UE005-8 400 - 460 - 575 V
three-phase
A
C
E
75...1250 μS
1 = A
2 = C
3 = E
26
Models UE025 to UE065
Fig. 9.e
power supply (V)
230
A
B
A
A
A
A
/
/
B
3
3
E
2
D
F
C
A
2
1
B
1
Fig. 9.f
UE005-8 / UE010-15
single-phase
200...230 V three-phase
A
A
B
F
B
F
C
E
C
E
D
D
350...1250 μS
75...350 μS
350...1250 μS
1 = A - B - C
1 = A - D
1 = A - B
2 = D - E - F
2 = B - E
2 = C - D
3 = C - F
3 = E - F
UE0010-18 400 - 460 - 575 V
three-phase
three-phase
A
A
C
E
C
E
75...1250 μS
75...1250 μS
1 = A
1 = A
2 = C
2 = C
3 = E
3 = E
A
400
B
B
B
B
A
B
A
B
Tab. 9.f
3
1

Publicidad

Capítulos

Tabla de contenido
loading