9 Help in the event of faults
9.2
Fault indicator
Channel 1 and 2 not
connected
Channel 3 and 4 not
connected
Channel 5 and 6 not
connected
Channel 7 and 8 not
connected
U software boundary
exceeded
I software boundary
exceeded
Delay active
Error in SMU 1
Error in SMU 2
62
LED indicator is flickering
LED indicator is off

Can be detected in the ControlCenter

The messages in the ControlCenter can be divided into fault messages
and status messages. Status messages report the current situation. If a
status message is marked in red, this indicates a warning of a temporary
fault. Monitor the component and begin troubleshooting if the message
appears continuously. After updating the display, this status message may
appear green again and there is no need for further action.
The left-hand third of the display in the ControlCenter provides an
overview of the fault and status messages. If the ControlCenter displays a
fault, consult the messages for the string monitoring units (also called
relay modules) to determine the details, and implement the appropriate
measures. Ensure that two inputs and their strings are assigned to each
string monitoring unit.
SmartConnect device status
Meaning
Relays for strings 1 and 2 are
|
switched off, strings are not
supplying any energy.
Relays for strings 3 and 4 are
|
switched off, strings are not
supplying any energy.
Relays for strings 5 and 6 are
|
switched off, strings are not
supplying any energy.
Relays for strings 7 and 8 are
|
switched off, strings are not
supplying any energy.
At least one string has exceeded
|
the voltage threshold value.
At least one string has exceeded
|
the current threshold value.
At least one string monitoring
|
unit is in delay status.
Fault in the string monitoring unit
|
(SMU).
Fault in the string monitoring unit
|
(SMU).
Action
Check the fault message for the
|
string monitoring unit.
Wait and monitor the situation.
|
Check the fault message for the
|
string monitoring unit.
Check the dimensioning of the
|
strings.
Check the fault message for the
|
string monitoring unit.
Wait. If there is no longer any
|
fault, the relay switches itself
back on.
Check the fault message for the
|
SMU.
Check the fault message for the
|
SMU.