1___TECHNICAL SPECIFICATIONS

SIZE:
CLASS OF PROTECTION:
CROSS-SECTION OF TERMINALS:
POWER SUPPLY REQUIREMENTS:
ABSORPTION:
MAX. CAPACITY ON RELAYS:
WORKING TEMPERATURE
STORAGE TEMPERATURE
1.1
SCALE OF MEASUREMENT OF THE pH:
INPUT IMPEDANCE:
TEMPERATURE OFFSETTING:
CONTROL OVER SET POINT:
Remote repetition of the measurement:
SCALE OF MEASUREMENT OF Cl:
TEMPERATURE OFFSETTING:
PH OFFSETTING:
CONTROL OVER SET POINT:
RE-TRANSMITTED OUTPUT :
N.B.
In swimming-pool water treated with DICHLOR or TRICHLOR-isocyanate it is
important to provide a good change of the water so that the residual isocyanate acid will
not exceed 50 ppm in order to ensure correct chlorine measurement.
240 mm – 245 mm – 140 mm
IP65 PROTECTING THE BNC OF THE PH electrode
2
4mm
, or diameter 2.4 mm
standard 230V
10% 50-60 Hz, on request 115V
15W
3A 250VAC (with resistive load)
0 to 50 ° C
-10 to 70 °C
0...14.00 pH
13
> 10
ohm
MANUAL/AUTOMATIC 0 to 125 °C
ON/OFF
BREAK/WORK
CURRENT, PROPORTIONAL
0/4 to 20 mA galvanically separated
Can be fully configured for re-transmission of measurement or control
Resolution 255 points
Maximum load 1 K Ohm
0 to 5.00 ppm or mg/l
Excludable
MANUAL/AUTOMATIC 0 to 125 °C
Excludable
Range of compensation 6 to 8.35 pH
ON/OFF
BREAK/WORK
CURRENT, PROPORTIONAL
0/4 to 20 mA galvanically separated
Can be fully configured for re-transmission of measurement or control
Resolution 255 points
Maximum load 1 K Ohm
3