baltur COMIST 122 DSPGM Manual De Instrucciones página 33

Ocultar thumbs Ver también para COMIST 122 DSPGM:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
Control programme
t
5s
Circuit to be checked put under atmospheric pressure
4
t
7.5 s
Time between start-up and "AR" main relay excitation
6
t
22.5 s
1° check phase with atmospheric pressure
1
t
5s
Gas circuit to be checked put under pressure
3
t
27.5 s
2nd check phase with gas pressure
2
t
67.5 s
Total duration of seal test, up to burner operation consensus
5
t
22.5 s
Return to the programmer stand-by position = preset for a new check.
20
Programme execution
AL remote alarm signal
AR main relay with 'ar...' contacts
AS device fuse
BR blocking relay with 'br...' contacts
DW external pressure switch (seal check)
EK release button
GP external pressure switch (of network gas pressure)
HR auxiliary relay with 'hr...' contacts
L1 device fault warning light
SK line switch
I ... XI
31 / 32
0006080115_201201
programmer cam contacts
Activated terminals of
equipment or electric
connections

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Comist 180 dspgmComist 250 dspgmComist 300 dspgm

Tabla de contenido