Electrical Connection; Connector Sr32; Connector Sr115; Cable Connection - Balluff BTL5-S1 Serie Manual De Instrucciones

Sistema magnetostrictivo de medición de posición – forma constructiva de varilla
Ocultar thumbs Ver también para BTL5-S1 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

BTL5-S1 _ _ (B)-M _ _ _ _ -K(8)-SR32/SR115/K_ _/F_ _
Magnetostrictive Linear Position Sensor – Rod Style
4
Installation and connection (continued)
Supporting rod made of non-magnetizable material
Fig. 4-7:
Example 2, BTL installed with supporting rod
4.4

Electrical Connection

Depending on the model, the electrical connection is made
using a cable or a connector.
The connection or pin assignments for the respective
version can be found in Tab. 4-2 to Tab. 4-4.
Note the information on shielding and cable
routing on page 11.
4.4.1

Connector SR32

Pin
BTL5-S1_ _...-SR32
1
+Clk
2
+Data
3
–Clk
4
Not used
1)
5
–Data
6
GND
7
20...28 V
8
Not used
1)
Unassigned leads that are not used can be connected to the GND on
1)
the controller side but not to the shield.
Tab. 4-2:
Connection assignment BTL5-...-SR32
Fig. 4-8:
Pin assignment of SR32 (view from above on BTL), 8-pin
M16 circular plug
10
english
Magnet
(e.g. BTL-P-1028-15R)
4.4.2

Connector SR115

Pin
BTL5-S1_ _...-SR115
1
+Clk
2
+Data
3
–Clk
4
Not used
1)
5
–Data
6
GND
7
20...28 V
8
Not used
1)
Unassigned leads that are not used can be connected to the GND on
1)
the controller side but not to the shield.
Tab. 4-3:
Connection assignment BTL5-...-SR115
Fig. 4-9:
Pin assignment of SR115 (view from above on BTL), 8-pin
M12 circular plug
4.4.3

Cable connection

Wire color
YE
Yellow
PK
Pink
GY
Gray
GN
Green
BU
Blue
BN
Brown
WH White
1)
Unassigned leads that are not used can be connected to the GND on
the controller side but not to the shield.
Tab. 4-4:
Cable assignment BTL5-...-cable
BTL5-S1_ _...-K_ _/F_ _
+Clk
–Clk
+Data
–Data
GND
20...28 V
Not used
1)

Publicidad

Tabla de contenido