Acknowledging Errors - Wilo Stratos GIGA Serie Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Stratos GIGA Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Classifica-
No.
tion
Communica-
E050 BMS communication
tion error
E051 Impermissible DP/MP
E052 DP/MP communica-
Electronics
E070 Internal communica-
faults
E071 EEPROM error
E072 Power section/fre-
E076 Internal transformer
E077 24 V operating voltage
E096 Infobyte not set
E097 Flexpump data record
E098 Flexpump data record
E110 Motor synchronization
E111 Excess current
E112 Excess rotation speed Internal electronics error
System
E119 Turbine operation
errors
11.3

Acknowledging errors

General
6.0.0.0
E000
6.0.0.0
10
1/1
S
Fig. 50: Navigation in case of error
Installation and operating instructions Wilo-Stratos GIGA
Error
Cause
Bus communication
time-out
interrupted or timed out
Cable break
Different pumps
combination
Cable MP communication
tions time-out
defective
Internal electronics error
tion error (SPI)
Internal electronics error
Internal electronics error
quency converter
Internal electronics error
defective
Sensor defective or con-
for sensor defective
nected incorrectly
Internal electronics error
Internal electronics error
missing
Internal electronics error
invalid
Internal electronics error
error
Internal electronics error
The flow is driving the
error (flow in flow
pump impeller; electrical
direction; pump can-
current is being fed back
not start)
to the mains
In the event of an error, the error page is displayed instead of the sta-
E000
tus page.
5.0.0.0
In this case, the following procedure can generally be used for naviga-
tion (Fig. 50):
• To change to menu mode, press the red button.
Menu number <6.0.0.0> flashes on the display.
By turning the red button, it is possible to navigate in the menu as
usual.
• Press the red button.
Menu number <6.0.0.0> appears steady on the display.
On the units display, the current incidence (x) as well as the maximum
incidence of the error (y) are displayed in the format "x/y".
Until the error can be acknowledged, pressing the red button again
will cause a return to menu mode.
Remedy
Check cable connection to
building automation
Request customer service
Check cable and cable connec-
tions
Request customer service
Request customer service
Request customer service
Request customer service
Check differential pressure
sensor connection
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Check the setting; check sys-
tem for proper operation Cau-
tion! Prolonged operation can
cause damage to the module
English
Error type
HV
AC
F
F
F
F
E
E
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B
A
B
A
B
A
A
A
59

Publicidad

Tabla de contenido
loading

Tabla de contenido