Wilo Stratos GIGA Serie Instrucciones De Instalación Y Funcionamiento página 69

Ocultar thumbs Ver también para Stratos GIGA Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

11.3.3 Error type C
1
2
3
4
5
6
7
8
Fig. 57: Error type C, diagram
6.0.0.0
E000
6.0.0.0
- - -
3/6
6.0.0.0
300
5/6
6.0.0.0
0
6/6
Fig. 58: Acknowledge error type C
Installation and operating instructions Wilo-Stratos GIGA
Error type C (Fig. 57):
Program
step/query
1
2
3
4
5
6
7
8
If type C errors occur, proceed as follows to acknowledge (Fig. 58):
• To change to menu mode, press the red button.
Menu number <6.0.0.0> flashes on the display.
• Press the red button again.
Menu number <6.0.0.0> appears steady on the display.
On the value display, "- - -" appears.
E000
On the units display, the current incidence (x) as well as the maximum
12.3
S
incidence of the error (y) are displayed in the format "x/y".
After 300 seconds, the current incidence will be counted up by one.
NOTE:
E000
12.3
The error will be acknowledged automatically if the cause of the error
S
is eliminated.
• Wait until the remaining time is up.
If the current incident (x) is the same as the maximum incidence of the
12.3
S
error (y), this error can be acknowledged manually.
• Press the red button again.
The error is acknowledged, and the status page is displayed.
Contents
• Error code is displayed
• Motor off
• Red LED on
Error criterion fulfilled?
> 5 minutes?
• Error counter is incremented
Error counter > 5?
• SSM is activated
Error acknowledged?
End; auto control resumes
yes
no
English
63

Publicidad

Tabla de contenido
loading

Tabla de contenido