Terminals
Fig. 30: Control terminals
Fig. 31: Power terminals (mains connection
terminals)
92
• Observe the rating plate information for the pump. The current type
and voltage of the mains connection must correspond to the details
on the rating plate.
• Fuse on mains side: max. 25 A
• Take additional earthing into account!
• The use of a miniature circuit breaker is recommended.
NOTE:
Miniature circuit breaker tripping characteristic: B
• Overload: 1.13–1.45 x I
• Short-circuit: 3-5 x I
nominal
• Control terminal (Fig. 30)
(See following table for assignment)
• Power terminals (mains connection terminals) (Fig. 31)
(See following table for assignment)
nominal