Terminal Box Positions - Grundfos MTC Serie Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.3.1 Torque for terminal box cover screws
Torque: 1.18 - 1.48 lbf-ft (1.6 - 2 Nm).
3.3.2 Motor protection
Single-phase motors
Single-phase motors are supplied with built-in
thermal protection, according to IEC 60034-11,
against thermal overload with both rapid and slow
variation.
Three-phase motors
Three-phase motors must be protected by a motor-
protective circuit breaker according to local
regulations.
ML motors as from 5 hp (3.0 kW) are supplied with
thermal switches (PTC) as standard and protected
against thermal overload with both rapid and slow
variation. The motor protection is stated on the
nameplate.

3.3.3 Terminal box positions

The terminal box can be turned to three positions, in
90 ° steps. See fig. 8.
Proceed as follows:
1. Remove the four bolts securing the motor to the
motor stool.
2. Turn the motor to the required position.
3. Refit and tighten the four bolts.
The electric motor must be connected to the supply
as shown in the diagram inside the terminal box
cover.
Position 3
Position 6
o'clock
o'clock
Fig. 8
Terminal box positions, top view
8
Position 9
Position 12
o'clock
o'clock
3.3.4 Plug connections
The pumps can be fitted with a 10-pin multiplug
®
connection, type Han
The purpose of a multiplug connection is to make the
electrical installation and the service of the pump
easier.
Fig. 9
Multiplug connection on a Grundfos
motor
6
7
W2 U2
V2
U1
V1
W1
1
2
Fig. 10
Connections between motor terminals
and plug terminals
L1
L2
1
2
6
7
Fig. 11
Plug connections for star connection
L1
L2
1
2
7
6
Fig. 12
Plug connections for delta connection,
fishplates for connections are located in
the plug
10 ES.
8
9
10
3
4
5
L3
3
4
5
8
9
10
L3
3
5
4
8
9
10