xChargeIn
7.4.1
Connection diagram
Fig. 7-17: Connection diagram X1
7.5
Switch contact output X2
This function is not available with xChargeIn A Series.
The switch contact output X2 (signal contact) is a floating relay contact and
can be used as a charging status display (default use) or contactor monitor-
ing. The terminal is designed as a spring-type terminal.
The use of the switch contact output must be activated with a DIP switch set-
ting (DSW1.2 to ON).
●
●
For further information see
Installation manual V1.05
© EATON
RFID
DSW 1.1
xChargeIn X Series and S Series (without charging net-
work)
Charging enabled when X1 is closed OR RFID authorization is
correct. The state of X1 is no longer checked during the charg-
On
OFF
ing process. The charging process can only be ended early us-
ing an RFID card.
If no RFID cards have been taught in, charging is possible at all
times, both with an open and closed X1.
xChargeIn X Series and S Series (without charging net-
work)
Charging enabled with X1 closed AND correct RFID authoriza-
On
ON
tion.
If no RFID cards have been taught in, charging takes place with
a closed X1.
xChargeIn S Series (in a charging network) and M Series
On
OFF
Charging enabled with correct RFID authorization.
No access is possible without an RFID card.
xChargeIn S Series (in a charging network) and M Series
Charging enabled with X1 closed AND correct RFID authoriza-
On
ON
tion.
No access is possible without an RFID card.
DSW1.2 OFF means X2 is used as the charge status indicator.
DSW1.2 ON means X2 is used as contactor monitoring.
Description
8.1 DIP switch
settings.
Connections and wiring
289