The process display records an analogue measured value. This
value can be monitored using a max. 2 alarm set points.
A clear readable two colour LED display shows the value in
digital and bargraph from. Set point infringements are
permanently displayed. The analogue output retransmits the
displayed value as either a current or voltage signal.
Transmitters connected can be directly supplied with power
from the unit.

2. Mechanical installation

Installation hints:
- The installation area must be vibration free.
- The permissible operating ambient temperature
is -10 to +50°C.
- Protect the unit from heat sources.
Panel installation:
Prepare a panel cut out of 45
Installation depth of the unit is 150 mm.
À
Push the unit through the gasket and the front of the
panel cutout.
Á
Hold the unit horizontally and fix the jackscrews to their
respective slots (top and bottom).
Â
Tighten the jackscrews evenly using a screwdriver.
+0,8
92
mm
LIMIT 1
LIMIT 2
96 mm
+0.6
+0.8
x 92
mm (to IEC 61554).
Process display