Parameter
Curve
On current/voltage input
signals enter the
connection between the
sensor signal and the
value to be displayed
On temperature inputs the
engineering units for the
display are indicated
Signal damping
τ
Filter constant
in sec.
for damping the input
signal
* Sensor decimal point
Number of decimal points
on sensor scale
* Sensor scale 0%
Sensor measurement
range
* Sensor scale 100%
Sensor measurement
range
* Cold junction
temperature
Selection between
internal and external cold
junction compensation
temperature on
thermocouples
* Constant
comparison temp.
Enter the constant
comparison temperature
on thermocouples
Setting up selections
CURVE
* Current/voltage input signal:
LINAR
linear input
signal
5QRT
Square root of a
squared input signal
TABLE
Presettable
linearization table
* Temperature input:
°C
Degrees Celsius
°F
Degrees Fahrenheit
DAMP
Value:
0 to 99
(low pass)
5c DP
Selection range:
0 to 4 decimal points
Sc LO
Values:
-19999 to 99999
Sc HI
Values:
-19999 to 99999
COMPT
INT
Compensation
temperature
measured with
internal sensor
CONST
Fixed compensation
temperature
FTMP
Value:
0 ... 200
Process display
Default
Actual
settings
LINAR
°C
0
999,9
0,0
100,0
INT
0
55