signal. On system fault the analogue output transmits a fault
signal of 21.0 mA.
Example:
Empty container:
- Sensor signal 4 mA
- Filling height 0 m
- Numeric display is to
show 0 (m³)
- Bargraph is to show
0%
- The analogue output
is to be 0 mA
Full container:
- Sensor signal 20 mA
- Filling height 10 m
- Numeric display is to show 1500 (m³)
- Bargraph is to show 100%
- The analogue output is to be 20 mA
Further entries:
Sensor
X1
value (m)
0,0
Display
Y1
value (m³)
0
- The analogue output is to ramp to 21.0 mA in fault condition
Menu group
INPUT
Analogue input
DISPL
Display
OUTPT
Analogue output
TABLE
Table
X2
X3
X4
0,2
0,4
0,6
Y2
Y3
Y4
20
50
85
Address
Input range
Curve
Decimal point Sensor
Sensor scale 0%
Sensor scale 100%
Decimal point
Display value 0%
Display value 100%
Scale bargraph/analog 0%
Scale bargraph/analog 100%
Output range
Fault operation
Number of linearization pionts
Display linearisation points
X5
X6
X7
0,8
1,0
1,2
Y5
Y6
Y7
115
160
210
RANG
CURVE
SC DP
SC LO
SC HI
DI DP
DI LO
DI HI
BG LO
RANG
FAIL
LSHOW
Process display
X8
X9
X10
1,4
1,6
10,0
Y8
Y9
Y10
280
400
1500
Value
4-20
TABLE
999,9
0,0
10,0
9999
0
1500
0
1500
BG HI
0-20
MAX
10
COUNT
YES