Example:
Input/Output:
- Input thermocouple Type S
- Internal temperature compensation
- 1100°C equals 4 mA
- 1300°C equals 20 mA
- Fault condition equals 3.6 mA at the analogue output
Set point 1:
- Minimum safety
- Switch point 1150 (°C)
- Hysteresis 10 (°C)
Set point 2:
- Minimum safety
- Switch point 1100 (°C)
- Hysteresis 50 (°C)
Setting up:
Menu group
INPUT
Analogue input
DISPL
Display
OUTPT
Analogue output
Set point/fault monitor
Set point/fault monitor
Address
Input range
Curve
Comparison temperature
Scale bargraph/analog. 0%
Scale bargraph/analog. 100%
Output range
Fault operation
LIM1
Mode
Set point
Hysteresis
LIM2
Mode
Set point
Hysteresis
RANG
CURVE
COMPT
RANG
FAIL
MODE1
SETP1
HYST1
MODE2
SETP2
HYST2
Process display
Value
TYPE5
°C
INT
1100,0
BG LO
1300,0
BG HI
4-20
MIN
MIN
1150,0
10,0
MIN
1100,0
50,0
69