Temperature Measurement In A Furnace - Endress+Hauser RIA250 Manual De Instrucciones

Ocultar thumbs Ver también para RIA250:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 194
Process display
Menu group
Linearization point address
Linearization point address
Linearization point address
.
.
.
Linearization point address
Linearization point address
The entry sequence is random because the points are
automatically sorted to the X-values upwards before being
saved. If further points need to be added then the value in
COUNT
addresses X10, Y10 and X11, Y11 are then added to the list in
front of the last value.
The other points can be entered in the new addresses
independent of sequence.
The added values are automatically sorted into the linearization
point sequence before being saved.

6.4 Temperature measurement in a furnace

The temperature in a furnace is being measured using a
thermocouple Type S (PtRh-Pt) and displayed. The range of
1100°C to 1300°C is to be retransmitted to a DCS in the form of
a 4-20 mA current signal. A warning lamp illuminates should
the value go below 1150°C, below 1100°C the material feeder
is switched off.
In fault condition the current signal ramps to minimum safety.
The terminal temperature compensation point is used for cold
junction compensation.
68
Address
NO 01
K1
will be automatically created and
cannot be changed
Y1
will be automatically created and
cannot be changed
NO 02
K2
Y2
NO 03
K3
Y3
.
.
.
NO 09
K9
Y9
NO 10
K10
will be automatically created and
cannot be changed
Y10
will be automatically created and
cannot be changed
must be increased e.g. from 10 to 12. The new
Value
0,0
0
0,2
20
0,4
50
.
.
.
1,6
400
10,0
1500

Publicidad

Tabla de contenido
loading

Tabla de contenido