Process display
The display
Fault signal analysis -
shows: "——-"
When using a 4-20 mA input
range the input signal from the
sensor is outside the specified
range (> 3.6 to < 3.85 mA or
> 20.4 to < 21.0 mA)
The 7 segment
The displayed measured
display shows a
value is > 10 % under the 0%
measured
value of the analogue output.
value, all Bar
graph LEDs are
off, the left LED
flashes.
The 7 segment
The displayed measured
display shows a
value is > 10% over the 100%
measured
value of the analogue output.
value, all Bar
graph LEDs are
off, the right
LED flashes.
The display
Setting of the comma position
E 290
shows: "
"
is not possible, as minimum
one digital value cannot be
displayed.

8. PC operating software

An operating manual for the PC operating software can be
found on the programme installation medium.
72
E 213
Please check the sensor
connected to the input for
correct operation.
E 240
Check if a valid input signal is
connected, or set a smaller
value to the 0% analogue
output value (
E 241
Check if a valid input signal is
connected, or set a larger
value to the 100% analogue
output value (
E 290
Acknowledge using the "E"
push button (Fault message
is deleted). Check all values
with this comma position and
reduce if required.
BG LO
BG HI
,
).
BG LO
BG HI
,
).