Idiomas disponibles

FUEL FEEDING HYDRAULIC DIAGRAM FOR ONE OR MORE LIGHT OIL BURNERS WITH MAXIMUM NOMINAL
VISCOSITY (5 °E at 50 °C)
1
2
3
4
6
7
8
9
10 Pressure gauge (0 - 4 bar)
DIAGRAM OF PIPES OF FEED SYSTEM FOR LIGHT OIL BURNERS WITH MAXIMUM NOMINAL VISCOSITY (5 °E at 50 °C)
1
2
3
4
5
6
7
8
Main cictern
Filter
Circulation pump
Water and system drain
Fuel recovery and degasifier
One-way valve
By-pass (usually closed)
Feeding circuit presure regulator adjustment range
between 0.2 and 1 bar
Main cictern
Filter
Circulation pumps
Water and system drain
Air-gas drain usually closed
Fuel recovery and degasifier
One-way valve
By-pass (usually closed)
0006080115_200909
The combustible recovery and degasifier tanks (diameter ~
150, height ~ 400) should be installed as near as possible to
the burner and should be about 0,5 m. higher with respect
to the burner's pump.
The combustible recovery and degasifier tanks (diameter ~ 150,
height ~ 400) should be installed as near as possible to the burner and
should be about 0,5 m. higher with respect to the burner's pump.