Quick User Manual
Type
SG2K-S / SG3K-S /
SG3K-D
SG4K-D / SG5K-D /
SG6K-D
SG8K3-D
Make sure to disconnect the AC circuit breaker and secure it against
reconnection before cable connection.
1
4
Terminal block
Housing
Cable gland
3.4 PV Connection
There is a risk of inverter damage! The following requirements should
be met. Failure to do so will void guarantee and warranty claims.
Make sure that the maximum short circuit current of each DC input is
less than inverter allowable limit.
Make sure that the maximum open voltage of each string is less than
600 V. Voltage over 600 V can damage the inverter.
Make sure that the impedances between the positive terminal of the
PV string and Earth, and the impedances between the negative
terminal of the PV string and Earth are larger than 200 kΩ in any
case.
All PV cables are equipped with the water-proof direct plug-in connectors which
match the PV terminals at the bottom of the inverter.
Cross-section (mm² )
Range
Recommended
4...6
4
4...6
6
-
6
2
8 mm
40 mm
"Click"
3 Electrical Connection
Cable diameter (mm)
Range
Recommended
10...14
14
10...14
14
-
15
3
.
(0.8 N m)
15 mm
–
PE
L
N
5
"Click"
9