SICK T4000 Standard Instrucciones De Operación página 136

Ocultar thumbs Ver también para T4000 Standard:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

5
Chapter
Fig. 2:
Evaluation of the
safety outputs
WARNING
136
© SICK AG • Industrial Safety Systems • Germany • Subject to change without notice
Electrical connection
T 4000 Evaluation Unit
Operating voltage
+ 24 V
0 V
DC
brown
If a common voltage supply is used, all of the
inductive and capacitive loads (e.g. contactors)
connected to the voltage supply must be
connected to suitable suppressors.
The door signal output OUT must not be used as a
safety output.
It is not permitted to increase the length of the
sensor connecting cable.
The screen of the sensor cable (3 cm max. to be
stripped) must be connected to the earth of the
evaluation unit.
The signal outputs ERR and OUT and the
connection terminals for the read head H1/H2 are
not short-circuit proof.
Should the device not function after the operating
voltage has been connected (e.g. green STATE-
LED does not light); please return the unit
unopened to the manufacturer.
Only copper with a temperature resistance of
75 °C may be used for the wiring.
The screws for the connecting terminal must be
tightened to a tightening torque of 0.6 to 0.8 Nm.
Screen terminal
white
13
14
23
24
Operating Instructions
T4000
Sensor
Coded
actuator
Trans-
ponder
8009704/XN71/2013-09-04

Publicidad

Tabla de contenido
loading

Tabla de contenido