Commissioning and operation
6.1.1 Teach-in function for first actuator
(condition as delivered)
1.
Apply the operating voltage to the evaluation
unit – Fast blinking (approx. 4 Hz) of the green
LED
2.
Move the actuator towards the sensor (note
distance < S
commences; slow blinking (approx. 1 Hz) of the
green LED
3.
Teach-in operation complete (after 60
seconds) – green LED goes out
4.
The operating voltage applied to the evaluation
unit must then be disconnected for a minimum
of 10 seconds to activate the actuator code
taught in the evaluation unit.
6.1.2 Teach-in function for a new actuator
1.
Apply the operating voltage to the evaluation
unit.
2.
Move the new actuator towards the sensor
(note distance < S
commences; green LED blinks (approx. 1 Hz)
3.
Teach-in operation complete (after 60
seconds) – green LED goes out, new code is
saved and old code is deactivated.
4.
The operating voltage on the evaluation unit
must then be disconnected for a minimum of
10 seconds to activate the actuator code
taught in the evaluation unit.