Ingersoll Rand G330 Guía De Usuario Y Mantenimiento Manual página 39

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

16 - O O ptions c c onnected t t o t t he i i nterface
Option description
external start-up command
auto predisposition + external command
3ph+neutral or 1ph+N mains connection
battery charger (3 possible ratings)
water heater (3 poss. depending on supply V)
hooter
RS485 for monitoring or remote
management
option 3 module / CAN bus connection
additional engine kit (9 options) (*)
electro-flaps (DC or AC)
anti-condensation heater
EJP (switch, adv. warning and start-up)
1ph or 3ph fuel pump (control & power)
Air cooler (low level, disconnection)
differential protection and MX coil contr ol
CIC protection with remote contact and MX
coil control
bulk tank fuel pump (CF80, low level,
retention bund)
AMPG with optional RS485
option 4 module / CAN bus connection
three-alarm (OP,WT,OT) and module 4 kit
*)indication and fault/shutdown for oil temperature, low oil level,
water heater failure and alarm/warning for, oil pressure, water
temperature, oil temperature, air damper control, starter 2 control.
17 - S S orties r r elais
! Max switching voltage: 250Vac (277Vac for *)
! Mains and Stand-by contactor control outputs: 4.9A, 1500VA breaking capacity at cosϕ=0.7
! Electro-flaps outputs: 500mA & CIC remote contact:1A
! MX coil control output (*): 4.9A (optional relay on baseplate)
18 - T T ransistor o o utputs
! Protected against short-circuit
! Output for fuel solenoid/panel lighting: 700mA
! Other outputs: 300mA
19 - H H ardware c c onfiguration
! C14/C15 connector, auxiliaries voltage selection
! C7 dip-switch, RS485 terminator
! P3 dip-switch, CAN bus terminator
! Dip-switch selection for VDE option
20 - E E nvironment a a nd s s tandards
! Operating temperature: -15°C to +60°C
! Storage temperature: -20°C to +70°C
! Resistance to shocks: IK01, vibration: to CEI68-2-6
! Salt mist resistance : 96 hours according to EN68011-2-11
! Humidity : 95 % of humidity at 45°C.
! EMC :
- Generic standards EN50081-2 and EN50082-2
- Emissions EN55011 Class A
- Immunity EN61000-4.2, EN6100-4.3, EN61000-4.4, EN61000-4.6, EN61000-4.8, ENV50201
! CE mark, UL listed, CSA certified
CB
CB12
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
French only
x
x
x
x
x
x
x
x
x
9

Publicidad

Tabla de contenido
loading