Status Messages During Commissioning (Ss - BONFIGLIOLI Vectron ACTIVE CUBE Guia De Inicio Rapido

Ocultar thumbs Ver también para Vectron ACTIVE CUBE:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

F08
01
Electronics voltage too low, check control terminals.
04
Electronic voltage too high, check wiring of control terminals.
F11
00
Output frequency too high, check control signals and settings.
01
Max. frequency reached by control (voltage control), check deceleration ramps and connected
brake resistor
F12
01
Diagnosis error of function STO; at least one of the shut-down paths STOA and STOB is defective.
Check the devices connected to the shut-down paths; check wiring and EMC.
04
Software self-diagnosis has detected an internal error. Parameter
GB
describes the cause of the error.. Consult BONFIGLIOLI customer service.
05
Fault message of 5-second monitoring. Shut-down paths STOA and STOB were not actuated at the
same time, but with an offset of more than 5 seconds. Check addressing of shut-down paths or
control of protection provision.
F13
00
Earth fault at output, check filter and cabling.
10
Minimum current monitoring, check motor and wiring.
F14
01
Reference value on multifunction input 1 faulty, check signal.
07
Overcurrent on multifunction input 1, check signal.
7.2

Status messages during commissioning (SS...)

The following status messages are possible when Setup is run:
Status message
SS000
OK
SS001
PC Phase 1
SS002
PC Phase 2
SS003
STO
SS004
Parameter identifica-
tion
SS010
Setup already active
SS030
No Release
SS031
Error – check P. 259
SS032
Warning Phase
Asymmetry
SS099
Setup not carried out
yet.
74
Electronic voltage
Output frequency
Safety function STO
Motor connection
Control connection
Auto set-up routine has been carried out.
The plausibility check (PC) of the motor data is active.
The calculation of dependent parameters is active.
The parameter identification requires release on digital input STOA and STOB.
The rated motor values are checked by the parameter identification feature.
The setup routine via the control panel is being carried out.
The parameter identification demands the controller release on digital input
STOA and STOB.
Error during the auto set-up routine. Check value of
The parameter identification feature diagnosed an unbalance during the mea-
surements in the three motor phases.
Self-setup has not yet been carried out.
Quick Start Guide ACU 201, ACU 401, ACU 501, ACU 601
Error Environment 1
Meaning
Current Error
262
259.
05/16

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Acu401

Tabla de contenido