Warning and error messages during commissioning (SA.../SF...)
Code
SA000
No warning message present.
SA001
The value of the parameter
ter The maximum reference voltage is indicated on the nameplate of the frequency inverter.
SA002
For a three-phase motor, the calculated efficiency is in the limit range. Check the values entered for
parameters
Rated Voltage
SA003
The value entered for parameter
Check the value.
SA004
For three-phase motor, the calculated slip is in the limit range. Check the values for parameters
372 and
Speed
Code
SA011
Current control setting, no typical value; see Operating Instructions
SA012
Current control setting, no typical value at 2 kHz; see Operating Instructions
SA014
Current control setting, no typical value at 4 kHz; see Operating Instructions
SA018
Current control setting, no typical value at 8 kHz; see Operating Instructions
SA021
Stator resistance (SA021) or rotor resistance (SA022) is very high. The following causes are possible:
SA022
The motor cable cross-section is not sufficient.
The motor cables are too long.
The motor cables are not connected correctly.
The contacts are not in a proper condition (corrosion).
SA031
Shorten Motor Line using Switchfrequ. 16 kHz.
SA032
Shorten Motor Line using Switchfrequ. 12 kHz and higher.
SA033
Shorten Motor Line using Switchfrequ. 8 kHz and higher.
SA041
The slip speed was not determined correctly. Check the values for parameters
and
Rated Frequency
SA042
The slip speed was not determined correctly. Check the values for parameters
and
Rated Frequency
Code
SA051
The machine data for star connection were entered, the motor, however, is connected in delta. For star
operation, change the motor cable connection. For delta operation, check the entered rated motor valu-
es.
Repeat the parameter identification
SA052
The machine data for delta connection were entered, the motor, however, is connected in star. For
delta operation, change the motor cable connection. For star operation, check the entered rated motor
values.
Repeat the parameter identification
SA053
A phase asymmetry was measured. Check the cables at the terminals of the motor and the frequency
inverter for proper connection and check the contacts for corrosion.
SA054
Resolver offset not adjusted.
05/16
Warning messages during guided commissioning
Meaning / Measure
Rated Voltage
370,
Rated Current
Rated Cosinus Phi
375.
Rated Frequency
Warning messages after parameter identification
Meaning / Measure
375.
375.
Warning messages after parameter identification
Meaning / Measure
Quick Start Guide ACU 201, ACU 401, ACU 501, ACU 601
370 is out of the rated voltage range of the frequency inver-
371 and
Rated Mech. Power
374 is outside of the normal range (0.6 to 0.95).
376.
Rated
372
Rated Speed