5.1 INFORMATION ABOUT THE VALVE STATUS
The valve LED shows lighting information to inform the user about its status.
ACTUATOR OPERATIONAL STATUS
Actuator without power supply
Actuator with power supply
Actuator working (flashing LED)
Actuator with torque limit function ON, moving from ... to ...
(flashing LED)
Actuator in MANUAL mode (exceeded time)
Actuator without power and working with the BSR system.
MAX 3 minutes
Battery protection. Danger - The battery needs recharging.
BSR disabled.
Actuator with DPS
6.
BSR OPTION
Security system in case of electrical failure, the actuator which is fitted with the BSR plug-in failsafe system, will go to the
predetermined position: NO (Normally Open) or NC (Normally Closed).
IMPORTANT: It is recommended that the electric valve could have an independent fuse system to protect it from other electrical
elements in line as pumps.
ACTUATOR MODEL
Nº working operation without recharge, with 100% battery charge
Battery consumption / working operation
Recharge time / working operation
Full charge time 100%
Current / one working operation with battery
7.

SET UP AND OPERATION

If adhesive has been used for the pipe union, please check the drying conditions of the adhesive (recommended by the
manufacturer) before passing fluid through the installation.
First of all, let pass fluid at low pressure by the valve and check both positions, open and closed; if the installation is well done, it
must show no leakage. After this checking, the installation could work normally.
It is very important to purgue the air in the installation, if not the valve could not work correctly.
Respect always the system conditions recommended by the manufacturer (pressure, temperature, chemical resistance, etc.) in
the valve, pipes, fittings, etc. Conditions explained in the Cepex Technical Catalogue and in the Hydraulic concepts in the Cepex
website.
STD ELECTRIC BUTTERFLY VALVE
LED STATUS
OFF
In open position: Green
In closed position: Red
Opening: sequence Red/Orange
Closing: sequence Green/Orange
From open to close: sequence Red/Off
From close to open: sequence Green/Off
Symmetric sequence: Orange/Off
BSR NC: sequence Red/Off
BSR NO: sequence Green/Off
Asymmetric sequence Orange/Off
Stop: Blue
Opening: seq. Blue/Green
Closing: seq. Blue/Red
J4 S35
J4 S55
10
10
21 min
48 min
3,0 W
6,8 W
28 h
28 h
14 mA
31,6 mA
J4 S85
J4 S140
J4 S300
10
4
4
58 min
30 min
50 min
8,3 W
23 W
23 W
28 h
54 h
54 h
38,6 mA
15,1 mA
25,7 mA
9