12.7 Room temperature reading offset

If for any reason the chronothermostat must be installed in a position where the
measured room temperature may be affected (e.g. on a perimeter wall that on
average is colder in winter and hotter in summer than the rest of the house), the
device allows for a correction of the detected room temperature with 2 different
parameters both in Winter mode and in Summer mode.
Following the path Menu -> CONFIG SEt -> select the element OFFSET Set.
Press the OK button to confirm.
OFFSET for winter mode (0)
The display alternates the empty fields to be entered (----) with the current
temperature value.
Use the 2 button to enter positive values, and the 3 button to enter
negative values («-» sign).
Possible offset -3.0 °C (-5.4 °F) ÷ 3.0 °C (5.4 °F) by default 0.0 °C/°F = ----
With each selection, the display will propose the new offset value (e.g. 0.6 °C)
alternating with the read temperature value (e.g.: 21.2 °C)
Once the offset is entered, press the button «OK».
The display will show the OFFSET for Summer mode (1); proceed to enter the
offset following the procedure explained above or press the back button to exit.
To cancel potential previously adjusted temperature offsets,
place OFFSET in ----.