Auxiliary Input
The AUX IN terminal supports a dry-contact 24 VDC digital input to control the
SubDrive/MonoDrive unit. This terminal can be wired using the internal 24 VDC
supply or an external 24 VDC supply. When using an external 24 VDC supply,
the signal common of the external supply must be connected to the AUX INPUT (-)
terminal of the SubDrive/MonoDrive controller.
(+): 24 VDC switched input
Internal 24 VDC Supply
WET SENSOR
(+24)
-OR-
TRANSDUCER
(+24)
External 24 VDC Supply
Refer to the Advanced Setup section for more information about configuring this input.