Accessing the Drive

After making a successful connection to the drive, launch the FE Connect mobile app. The
FE Connect mobile app can be downloaded from the Apple App Store or Google Play,
depending on the device being used.

Set-up

The Set-up screen allows for the set-up of additional features of the drive including:
• Drive Output*
• Motor Size*
• Pump Size*
• Underload Sensitivity*
• Underload Off Time
• Minimum Frequency
• Maximum Frequency
* In order to change and use settings from this page for the Drive Output, Motor Size, Pump Size, Underload Sensitivity,
Pressure Sensor Type, Pressure Transducer Range, Pressure Set Point, Duplex Alternator Functionality, and Steady Flow, the
FE Connect DIP switch (SW1, Position 1) on the drive must be "ON". Otherwise, the drive will default to the settings made
via the DIP switches and Underload Sensitivity and Pressure Set Point rotary knobs on the drive itself.
The Pressure Control portion of the Setup screen allows for
configuration of the Sensor Type, Transducer Range, Primary
Setpoint, and Drawdown functions.
Pressure Control: Sensor Type
This parameter sets which pressure sensor type to use:
Switch, Transducer (PSI), or Transducer (bar).
Default: Transducer (PSI)
Pressure Control: Transducer Range
When using a pressure transducer, this parameter sets the
range of the transducer connected to the drive.
Default: 100 (PSI)
Minimum: 100 PSI
Pressure Control: Primary Setpoint
When using a pressure transducer, this parameter sets the
system pressure set point that the controller will regulate to.
Default: 50 PSI
Minimum: 5 PSI
Maximum: (Pressure Transducer Range) – 5 PSI
Pressure Control: Drawdown
This selection enables or disables the drawdown function.
Drawdown allows the drive to regulate to the Pressure
Setpoint and remain off until the Cut In Setpoint is reached.
Pressure Control: Cut In Setpoint
Also known as drawdown, this parameter sets the pressure
to which the system pressure must be reduced before the
controller will begin to run.
Default: 40 PSI
Minimum: 5 PSI
Maximum: (Pressure Setpoint) – 1 PSI
All manuals and user guides at all-guides.com
• Pressure Sensor Type*
• Pressure Transducer Range*
• Pressure Set Point*
• Drawdown / Cut-in Pressure
• Duplex Alternator Functionality*
• Moisture Sensor
Maximum: 300 PSI
SubDrive/MonoDrive Connect
• Bump Mode
• Large Tank Mode
• Aggressive Bump
• Broken Pipe Detection
• Steady Flow*
• Units (hp or kW)
Pressure Control
Transducer Range
Drawdown Enable
Sensor Selection
Primary Setpoint
Cut In Setpoint